Busrail System Issues Report

Beginning in October 2013, Panoptic Solutions has been inspecting and testing Bus Rail systems for a large (over 1 million square foot) data center operator. The following table summarizes the issues found during these preventative maintenance procedures.

As summarized above we inspected 3573 devices finding 196 issues representing a 5.5% incident rate.

Example Images:

This image shows a non- terminated wire inside bus plug

This image shows a non- terminated wire on load side of the breaker.

This image shows a loose wire left inside bus plug during the manufacturing process.

This is a thermal image indicating poor termination inside the stab to the busrail. Upon removal and inspection, it was determined a poor solder joint was the issue.

This is a thermal image indicating a poor connection in an In Feed.

This is a thermal image showing high heat on a power indicator light wire and a hot CT.

This image shows improperly connected monitoring system indicating poor quality control in the manufacturing process.

951 7th Street, Stu G.

  • Rochelle, IL 61068

By rleonard85 23 Jan, 2022
POWER QUALITY STUDY
By rleonard85 22 Jan, 2022
Non-Invasive Thermal Imaging Through Protective Grates
By rleonard85 22 Jan, 2022
Panoptic Solutions LLC 
By rleonard85 22 Jan, 2022
Panoptic Solutions LLC 
By rleonard85 22 Jan, 2022
Panoptic Solutions LLC 
By rleonard85 22 Jan, 2022
Watch List Exception Report
By rleonard85 22 Jan, 2022
Panoptic Solutions LLC 
By rleonard85 22 Jan, 2022
Panoptic Solutions LLC 
By rleonard85 22 Jan, 2022
Non-Invasive Thermal Imaging Through Protective Grates
By rleonard85 22 Jan, 2022
PANOPTIC SOLUTIONS LLC
More Posts
Share by: